Case Study: Heat Recovery

Manufacturer: HAAKON

Site: Hudson Alpha Institute of Biotechnology – Huntsville, Alabama

Size/Application: 79,000 CFM Energy Recovery Air Handling Units

Total CFM: 395,000

Equipment Features: 

  • Ion Exchange desiccant heat wheel to minimize odor transfer.
  • All welded steel tread plate floors
  • 4″ double-wall panel construction
  • Complete four quadrant factory leakage test (.25 percent CFM @ 10 inches w.g.)
  • Factory installed humidifier panels with 18″ low absorbtion distance
  • Factory installed fan personnel safety screens

Project Specifics: 
Units serve multi-story biotechnology laboratory for 100% outside air makeup. Units require custom design for small footprint.